Carrier · Furnace

14.3 Lockout - 7 flame-loss events in one heat call

High severity 59SC6A

What the control is telling you

The control saw 7 loss-of-flame events during one heating demand and locked out.

Applies to: Carrier 59SC6A

Likely causes

  • Weak flame signal (dirty sensor)
  • Unstable gas supply
  • Venting or combustion air restriction
  • Poor ground

Test and repair steps

  1. Warning: Turn off gas and power and lock out before removing burner parts.
  2. Clean the flame sensor with 0000 steel wool only (no sandpaper or emery cloth); check it sits in the flame.
  3. Verify ground continuity green/yellow wire to gas valve and manifold bracket screw, and the flame-sense ground wire to furnace sheet metal.
  4. Check natural gas supply (4.5-14 in. w.c.) while burning and manifold pressure (2.8-3.8 in. w.c. for 40k-120k models; max 1.8 in. w.c. on 26k).
  5. Inspect burners and orifices for dirt or blockage; clean burner with brush and vacuum.
  6. Inspect vent and combustion-air pipes for water, sags or blockage.
  7. Run 2 complete heat cycles and look at the flame: it should be clear blue, almost transparent.
  8. Reset the lockout by briefly removing 115 VAC power, or by breaking 24 VAC at SEC1/SEC2 on the control (not at W, G or R); otherwise it auto-resets after 3 hours.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier 59SC6A Installation, Start-up, Operating and Service Instructions, Fig. 60 Service Label p.54; Cleaning Burners and Flame Sensor p.66; Fig. 61 notes p.56. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.