Carrier · Furnace
inF Menu: program number and software
What the display is showing
Main menu item that alternates between the saved model program number (pRG) and the software version (uEr). Never load a program number that differs from the rating plate, or the airflow options will not match the furnace.
Applies to: 59SC6A, Payne PG96VTA and 59MN7C furnaces (3-digit display control)
What to do
- Scroll to inF with MENU/SELECT; the display alternates between the two values.
Settings for these units
Filter sizes by casing width and filter cabinet · 59SC6A
| Location | Size | Side return filter | Bottom return filter | Type |
|---|---|---|---|---|
| Furnace casing | 14-3/16 in. wide | 16 x 25 x 3/4 in. | 14 x 25 x 3/4 in. | Washable |
| Furnace casing | 17-1/2 in. wide | (1) 16 x 25 x 3/4 in. | (1) 16 x 25 x 3/4 in. | Washable |
| Furnace casing | 21 in. wide | (1) 16 x 25 x 3/4 in. | (1) 20 x 25 x 3/4 in. | Washable |
| Furnace casing | 24-1/2 in. wide | (1) 16 x 25 x 3/4 in. | (1) 24 x 25 x 3/4 in. | Washable |
| Filter cabinet | 16 in. high | (1) 16 x 25 x 3/4 in. or (1) 16 x 25 x 4-5/16 in. | - | Washable or media |
| Filter cabinet | 20 in. high | (1) 20 x 25 x 3/4 in. or (1) 20 x 25 x 4-5/16 in. | - | Washable or media |
| Filter cabinet | 24 in. high | (1) 24 x 25 x 3/4 in. or (1) 24 x 25 x 4-5/16 in. | - | Washable or media |
Side-return filters can differ in size - measure the existing filter.
Every return-air inlet needs a filter.
Minimum clearances to combustibles · 59SC6A
| Position | Minimum clearance |
|---|---|
| Rear | 0 |
| Front (combustion air openings in furnace and in structure) | 1 in. (25 mm) |
| Required for service | 24 in. (610 mm) (see note) |
| All sides of supply plenum | 1 in. (25 mm) (see note) |
| Sides | 0 |
| Vent | 0 |
| Top of furnace | 1 in. (25 mm) |
Service and supply-plenum values are marked 'consult local building codes'.
Keep 1 in. (25 mm) from combustibles to supply ductwork for 36 in. (914 mm) horizontally from the furnace.
- Filter sizes by casing width · Payne PG96VTA
Models that show this code
25 models in 59SC6A, Payne PG96VTA, 59MN7C
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 59SC6A installation instructions, Table 21 Main Menu Options, p.53; Payne PG96VTAB installation instructions, Main Menu Options table, p.53; Carrier 59MN7C installation instructions, Table 18 Main Menu Options, p.47. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.