Carrier · Furnace
11 No previous code
What the control is telling you
Shown at the end of the stored code history (1 short, 1 long flash). Codes are erased after 72 hours or manually.
Applies to: 59TP6A two-stage variable-speed ECM multipoise condensing gas furnace, all sizes (040-10 to 120-22)
Likely causes
- No stored faults / end of history list
Test and repair steps
- To read history disconnect the R thermostat wire, reset power, set SW1-1 ON. The LED flashes stored codes in order; record them until code 11 flashes, after which the list repeats.
- Warning: When holding the blower door switch closed for service, 115-V parts are exposed and live.
- To clear history manually with SW1-1 ON, jumper R, W/W1 and Y/Y2 at the same time until code 11 flashes.
- Set SW1-1 OFF and reconnect R.
- Run the system through low-heat, high-heat and cooling to check operation.
Settings for these units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 59TP6A Installation, Start-up, Operating and Service Instructions, Fig. 66 Troubleshooting Guide, p.88; p.77. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.