Navien tankless water heater error codes

64 codes (38 faults, 26 normal display and menu codes), plus 3 settings tables.

CodeMeaningSeverity / type
E003Ignition failureHigh
E004False flame detectionMedium
E012Flame lossHigh
E016Heat exchanger overheatingHigh
E21No hot waterMedium
E030Exhaust overheatingHigh
E031Burner overheatingCritical
E046Limit control abnormalHigh
E047Exhaust thermistor open or shortedMedium
E056Modulating gas valve faultHigh
E060Dual venturi abnormalHigh
E109Fan motor abnormalHigh
E110Abnormal air pressureHigh
E127Air pressure sensor (APS) faultHigh
E157Air volume control faultHigh
E170Antifreeze heater open or shortHigh
E407Hot water outlet thermistor open or shortedMedium
E421Cold water inlet 1 thermistor open or shortedMedium
E432Cold water inlet 2 thermistor open or shortedMedium
E434Water adjustment valve abnormalMedium
E438Circulation pump abnormal (with air handler)Medium
E439Flow sensor abnormalMedium
E441Hot water inlet 2 thermistor open or shortedMedium
E445Bypass mixing valve abnormalMedium
E515PCB abnormalHigh
E517DIP switch setting abnormalMedium
E593Front panel key abnormalLow
E594EEPROM abnormalHigh
E615Input and memory abnormalHigh
E736Cascade communication abnormalMedium
E740Outdoor temperature sensor abnormal (with air handler)Low
E760Flushing / service alarmLow
E762Vent pipe not properly insertedHigh
E773Wrong gas type detectedCritical
E782Main / panel communication abnormalMedium
E785Flow switch / sensor abnormal (with air handler)Medium
E786Abnormal operation: panel connectionHigh
E788Gas type mismatch: DIP switch vs panel settingMedium
CLRAll timers clearedNormal status
CombustionCombustion indicatorNormal status
Combustion/ErrorCombustion / error indicatorNormal status
Error iconError indicatorNormal status
GasPropane gas indicatorNormal status
HEATRecirculation started from remoteNormal status
Hot water recirculation iconHot water recirculation indicatorNormal status
Hot water set temperatureHot water temperature setting displayNormal status
ID 1. Allocated!Cascade sub unit ID assignedMenu / mode display
MA.00Cascade main unit confirmedMenu / mode display
MAINRemote asks for main/sub settingNormal status
Main/SubCascade main or sub unit indicatorNormal status
Master unit iconMaster unit (cascade) indicatorNormal status
Preheat iconRecirculation schedule / preheat iconNormal status
R&D information menuR&D information menu (Power off, key sequence)Menu / mode display
Recirculation mode displayRecirculation mode displayNormal status
Recirculation/Space HeatingRecirculation / space heating indicatorNormal status
Remote LEDRemote controller LED colourNormal status
Remote lock iconRemote lock mode onNormal status
SL.01Cascade sub unit confirmedMenu / mode display
SL.xxSub remote waiting for IDNormal status
SUBRemote set as subNormal status
SYNCRemote synchronizingNormal status
Service/Installer menuService / installer menu (Menu + Back)Menu / mode display
Start-up wizardFirst power-on start-up wizardMenu / mode display
Status/FlowOperation status and flow rate areaNormal status

Settings and specs

Installation clearances (indoor / outdoor)

Clearances · Navien NPE-2

SideIndoorOutdoor
Top9 in. (229 mm)36 in. (900 mm)
Back0.5 in. (13 mm)0.5 in. (13 mm)
Front4 in. (100 mm)24 in. (600 mm)
Sides3 in. (76 mm)3 in. (76 mm)
Bottom12 in. (300 mm)12 in. (300 mm)
  • Vent clearance to combustibles is 0 in.
  • Outdoor: use the Navien Outdoor Vent Kit; keep 3 ft from an eave to the top of the vent terminals; mild climates only.
  • Keep room temp between 32 F (0 C) and 125 F (52 C).
  • Common vent installs: 36 in. top and 24 in. front recommended for service.

Source: Navien NPE-A2/S2 Installation Manual, 3.1 Adequate Installation Clearances, p.17; Outdoor Installation, p.59

Water quality limits and flushing schedule

Water quality · Navien NPE-2

Hardnessgrains/gal (mg/L)TreatmentFlush frequency
Soft0-4 (0-60)NoneNone
Moderately hard4-7 (61-120)None requiredOnce a year
Hard7-9 (121-160)Softener or Navien PeakFlow recommendedOnce a year
Very hard9-12 (161-200)Softener or PeakFlow highly recommendedResidential once a year; commercial twice a year
Extremely hard>12 (200)Softener or PeakFlow required-
  • Other max levels: hardness 200 mg/L, chloride 250, copper 1.0, iron 0.3, manganese 0.05, sulfate 250, TDS 500, zinc 5, chlorine 4 mg/L; aluminum 0.05-0.2 mg/L; pH 6.5-8.5.
  • Flushing is advised when no treatment device is installed; use white vinegar or a tankless descaler.
  • Damage from poor water quality is not covered by warranty.
  • Manual's flush column for moderately hard to hard rows is merged - read as once a year.

Source: Navien NPE-A2/S2 Installation Manual, 3.1 About Water Quality, p.15

Installation clearances (indoor / outdoor)

Clearances · Navien NPN

SideIndoor: combustiblesIndoor: non-combustiblesOutdoor: combustiblesOutdoor: non-combustibles
Top6 in. (152 mm)2 in. (51 mm)12 in. (305 mm)2 in. (51 mm)
Back0 in.0 in.0 in.0 in.
Front6 in. (152 mm)6 in. (152 mm)Panel 24 in. (610 mm); exhaust 24 in. (610 mm)Panel 0 in.; exhaust 24 in. (610 mm)
Sides2 in. (51 mm)1/2 in. (13 mm)6 in. (152 mm)1/8 in. (3.2 mm)
Ground / bottom12 in. (305 mm)12 in. (305 mm)12 in. (305 mm)2 in. (51 mm)
Vent0 in.0 in.--
  • Room temp must stay between 32 F (0 C) and 120 F (49 C).
  • Outdoor models need a weather-rated disconnect switch for the 120 V supply.
  • Indoor models: rated to 10,100 ft (3,078 m). Outdoor models: under 4,500 ft only.

Source: Navien NPN-U/NPN-E Installation Manual, 3.1 Adequate installation clearances, p.17; 3.6, p.47; 3.7.2, p.49

Models covered

NHW700-120SENHW700-160AENHW700-160AINHW700-160SENHW700-160SUNHW700-180AENHW700-180AINHW700-180SENHW700-180SUNHW700-199AENHW700-199AINHW700-199SENHW700-199SUNPE-150S2NPE-180A2NPE-180S2NPE-210A2NPE-210S2NPE-240A2NPE-240S2NPN-120ENPN-160ENPN-160UNPN-180ENPN-180UNPN-199ENPN-199UNaviCirc

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.