Navien · Tankless water heater

E056 Modulating gas valve fault

High severity Navien NHW700

What the control is telling you

The control sees a problem with the modulating gas valve. Lock-out: needs a manual reset after the fix.

Applies to: NHW700-120SE/160SE/180SE/199SE, NHW700-160SU/180SU/199SU, NHW700-160AI/180AI/199AI, NHW700-160AE/180AE/199AE

Likely causes

  • Gas valve coil open or shorted
  • Loose or damaged wire or connector at the gas valve
  • PCB not sending the right voltage to the valve

Test and repair steps

  1. Gas unit only a qualified gas technician should work on it. Power off at the switch before unplugging any connector.
  2. Check the gray wires and plug at the modulating gas valve (diagnostic point F). The PCB drives it with a pulse signal.
  3. Unplug the valve and measure the coil resistance. Compare with the values in 7.3.15 (p.110).
  4. Coil reads open or way off replace the gas control valve.
  5. Valve reads good check the output from the PCB. No proper output: replace the PCB.
  6. Valve and PCB both check good reset the heater and run it.

Settings for these units

Models that show this code

13 models in Navien NHW700

NHW700-120SENHW700-160AENHW700-160AINHW700-160SENHW700-160SUNHW700-180AENHW700-180AINHW700-180SENHW700-180SUNHW700-199AENHW700-199AINHW700-199SENHW700-199SU

Other codes on the same units

  • E127 Air pressure sensor (APS) fault
  • E157 Air volume control fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NHW700 Non-Condensing Water Heater Service Manual (V1.0, Apr 2023), 7.1 p.88, 7.2 p.90, 7.3.6 p.101, 5.5 p.75. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.