Navien · Tankless water heater
E157 Air volume control fault
What the control is telling you
During pre-purge the control could not bring the air flow (read by the APS) up to the ignition level within 25 seconds, more than 10 times in a row. Needs a manual reset.
Applies to: NHW700-120SE/160SE/180SE/199SE, NHW700-160SU/180SU/199SU, NHW700-160AI/180AI/199AI, NHW700-160AE/180AE/199AE
Likely causes
- APS hose kinked or bent
- APS hose on the fan (minus) side damaged
- APS hoses on the wrong ports
- Fan not moving enough air
- Failed APS
- PCB fault
Test and repair steps
- Power off before unplugging connectors or measuring resistance.
- Straighten any kinked APS hose and look for cracks, mostly on the hose that goes to the fan (minus side).
- Check the plus and minus hoses are not swapped on the APS.
- Check the APS supply and signal voltages (5 V DC red-black, 0.3-4.5 V DC white-black).
- Hoses and APS check good but air flow stays low: replace the fan.
- Still there replace the APS, then the PCB if nothing else fixed it.
Settings for these units
- Installation clearances (indoor / outdoor) · Navien NPE-2
- Water quality limits and flushing schedule · Navien NPE-2
- Installation clearances (indoor / outdoor) · Navien NPN
Models that show this code
13 models in Navien NHW700
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NHW700 Non-Condensing Water Heater Service Manual (V1.0, Apr 2023), 7.1 p.88, 7.2 p.90, 7.3.10 p.105, 5.5 p.75. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.