Navien · Tankless water heater
E740 Outdoor temperature sensor abnormal (with air handler)
What the control is telling you
Outdoor reset is on but the outdoor sensor is missing or reads out of range.
Applies to: Navien NPE-A2 (built-in recirculation) and NPE-S2 condensing tankless water heaters: NPE-150S2, NPE-180A2/S2, NPE-210A2/S2, NPE-240A2/S2
Likely causes
- Outdoor sensor not connected
- Sensor or wiring fault
Test and repair steps
- Check the outdoor sensor wiring at the H2Air controller.
- If outdoor reset is not wanted, set H2Air DIP switch 1 ON (outdoor reset off). While the error is active the system runs as if outdoor reset were off.
- Check Status Information > 16. AHU Outdoor Temp.
- Fix given phone Navien Technical Support, 1-800-519-8794.
Settings for these units
- Installation clearances (indoor / outdoor) · Navien NPE-2
- Water quality limits and flushing schedule · Navien NPE-2
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NPE-A2/S2 User's Information Manual (20049624A), 5.2 Understanding Error Codes, p.18. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.