Navien · Tankless water heater

E110 Abnormal air pressure

High severity Navien NPE-2

What the control is telling you

The air pressure sensor (APS) detected a blocked or restricted air path.

Applies to: Navien NPE-A2 (built-in recirculation) and NPE-S2 condensing tankless water heaters: NPE-150S2, NPE-180A2/S2, NPE-210A2/S2, NPE-240A2/S2

Likely causes

  • Clogged air intake filter
  • Blocked exhaust or intake (debris, snow, ice, nests)
  • Vent run too long or too many elbows

Test and repair steps

  1. Make sure the exhaust pipe and termination are clear (manual's listed action).
  2. Clean the air intake filter (the manual says a clogged filter causes Error 110).
  3. Check vent length max 75 ft with 2 in. (6 elbows), 150 ft with 3 in. or 4 in. (8 elbows); subtract 8 ft per 90 deg elbow on 2 in., 5 ft on 3 in. or 4 in.
  4. Make sure terminations are at least 12 in. above the highest expected snow line.
  5. Check Status Information > 14. Current APS (APS voltage).
  6. Reset once with the Back button on the front panel and note whether the code returns.
  7. Code back after a reset? Stay at the unit and phone Navien Technical Support, 1-800-519-8794.

Settings for these units

Installation clearances (indoor / outdoor) · Navien NPE-2

SideIndoorOutdoor
Top9 in. (229 mm)36 in. (900 mm)
Back0.5 in. (13 mm)0.5 in. (13 mm)
Front4 in. (100 mm)24 in. (600 mm)
Sides3 in. (76 mm)3 in. (76 mm)
Bottom12 in. (300 mm)12 in. (300 mm)

Vent clearance to combustibles is 0 in.

Outdoor: use the Navien Outdoor Vent Kit; keep 3 ft from an eave to the top of the vent terminals; mild climates only.

Water quality limits and flushing schedule · Navien NPE-2

Hardnessgrains/gal (mg/L)TreatmentFlush frequency
Soft0-4 (0-60)NoneNone
Moderately hard4-7 (61-120)None requiredOnce a year
Hard7-9 (121-160)Softener or Navien PeakFlow recommendedOnce a year
Very hard9-12 (161-200)Softener or PeakFlow highly recommendedResidential once a year; commercial twice a year
Extremely hard>12 (200)Softener or PeakFlow required-

Other max levels: hardness 200 mg/L, chloride 250, copper 1.0, iron 0.3, manganese 0.05, sulfate 250, TDS 500, zinc 5, chlorine 4 mg/L; aluminum 0.05-0.2 mg/L; pH 6.5-8.5.

Flushing is advised when no treatment device is installed; use white vinegar or a tankless descaler.

Models that show this code

7 models in Navien NPE-2

NPE-150S2NPE-180A2NPE-180S2NPE-210A2NPE-210S2NPE-240A2NPE-240S2

Other codes on the same units

  • E031 Burner overheating
  • E046 Limit control abnormal
  • E047 Exhaust thermistor open or shorted
  • E060 Dual venturi abnormal
  • E109 Fan motor abnormal
  • E407 Hot water outlet thermistor open or shorted
  • E421 Cold water inlet 1 thermistor open or shorted
  • E432 Cold water inlet 2 thermistor open or shorted

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NPE-A2/S2 User's Information Manual (20049624A), 5.2 Understanding Error Codes, p.17. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.