Navien · Tankless water heater
MA.00 Cascade main unit confirmed
What the display is showing
Shown on the main heater when Diagnostic + Up (+) are held for more than 5 seconds, confirming it is set as the main unit of the two-heater cascade.
Applies to: NPN-160U/180U/199U, NPN-120E/160E/180E/199E
What to do
- Main unit hold Diagnostic + Up (+) for more than 5 s, MA.00 appears.
- Sub unit hold Diagnostic + Down (-) for more than 2 s, SL.01 appears.
- Main unit hold Diagnostic + Up (+) for 5 s again; displays return to temperature.
- To cancel, hold Diagnostic + Reset for 5 s on the main unit.
Settings for these units
Installation clearances (indoor / outdoor) · Navien NPN
| Side | Indoor: combustibles | Indoor: non-combustibles | Outdoor: combustibles | Outdoor: non-combustibles |
|---|---|---|---|---|
| Top | 6 in. (152 mm) | 2 in. (51 mm) | 12 in. (305 mm) | 2 in. (51 mm) |
| Back | 0 in. | 0 in. | 0 in. | 0 in. |
| Front | 6 in. (152 mm) | 6 in. (152 mm) | Panel 24 in. (610 mm); exhaust 24 in. (610 mm) | Panel 0 in.; exhaust 24 in. (610 mm) |
| Sides | 2 in. (51 mm) | 1/2 in. (13 mm) | 6 in. (152 mm) | 1/8 in. (3.2 mm) |
| Ground / bottom | 12 in. (305 mm) | 12 in. (305 mm) | 12 in. (305 mm) | 2 in. (51 mm) |
| Vent | 0 in. | 0 in. | - | - |
Room temp must stay between 32 F (0 C) and 120 F (49 C).
Outdoor models need a weather-rated disconnect switch for the 120 V supply.
Models that show this code
7 models in Navien NPN
Other codes on the same units
- Error icon Error indicator
- HEAT Recirculation started from remote
- Hot water recirculation icon Hot water recirculation indicator
- MAIN Remote asks for main/sub setting
- Master unit icon Master unit (cascade) indicator
- Preheat icon Recirculation schedule / preheat icon
- R&D information menu R&D information menu (Power off, key sequence)
- Recirculation mode display Recirculation mode display
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NPN-U/NPN-E Installation Manual, 5.2.1 Configuring the Communication Settings, p.58. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.