Navien · Tankless water heater

E788 Gas type mismatch: DIP switch vs panel setting

Medium severity Navien NPE-2

What the control is telling you

The gas type on front-panel DIP switch 1 does not match the gas type stored in the panel. Expected right after changing DIP switch 1 during a conversion.

Applies to: Navien NPE-A2 (built-in recirculation) and NPE-S2 condensing tankless water heaters: NPE-150S2, NPE-180A2/S2, NPE-210A2/S2, NPE-240A2/S2

Likely causes

  • DIP switch 1 changed (gas conversion)
  • Panel gas setting not updated

Test and repair steps

  1. Confirm the gas supplied and the rating plate.
  2. Set DIP switch 1 OFF natural gas, ON propane (power off when changing).
  3. Power on; in the error screen press Back to open Gas Type Check in the Start-Up Wizard and select the gas type.
  4. On propane, accept the Gas Conversion Kit Required prompt. The error then clears and the unit fires.
  5. After any conversion, check CO2 or the low-fire offset pressure against the conversion tables.

Settings for these units

Installation clearances (indoor / outdoor) · Navien NPE-2

SideIndoorOutdoor
Top9 in. (229 mm)36 in. (900 mm)
Back0.5 in. (13 mm)0.5 in. (13 mm)
Front4 in. (100 mm)24 in. (600 mm)
Sides3 in. (76 mm)3 in. (76 mm)
Bottom12 in. (300 mm)12 in. (300 mm)

Vent clearance to combustibles is 0 in.

Outdoor: use the Navien Outdoor Vent Kit; keep 3 ft from an eave to the top of the vent terminals; mild climates only.

Water quality limits and flushing schedule · Navien NPE-2

Hardnessgrains/gal (mg/L)TreatmentFlush frequency
Soft0-4 (0-60)NoneNone
Moderately hard4-7 (61-120)None requiredOnce a year
Hard7-9 (121-160)Softener or Navien PeakFlow recommendedOnce a year
Very hard9-12 (161-200)Softener or PeakFlow highly recommendedResidential once a year; commercial twice a year
Extremely hard>12 (200)Softener or PeakFlow required-

Other max levels: hardness 200 mg/L, chloride 250, copper 1.0, iron 0.3, manganese 0.05, sulfate 250, TDS 500, zinc 5, chlorine 4 mg/L; aluminum 0.05-0.2 mg/L; pH 6.5-8.5.

Flushing is advised when no treatment device is installed; use white vinegar or a tankless descaler.

Models that show this code

7 models in Navien NPE-2

NPE-150S2NPE-180A2NPE-180S2NPE-210A2NPE-210S2NPE-240A2NPE-240S2

Other codes on the same units

  • E760 Flushing / service alarm
  • E762 Vent pipe not properly inserted
  • E773 Wrong gas type detected
  • E782 Main / panel communication abnormal
  • E785 Flow switch / sensor abnormal (with air handler)
  • CLR All timers cleared
  • Combustion/Error Combustion / error indicator
  • Gas Propane gas indicator

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NPE-A2/S2 User's Information Manual (20049624A), 5.2 Understanding Error Codes, p.18; Navien NPE-A2/S2 Installation Manual, 8.1, p.112. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.