Navien · Tankless water heater
E012 Flame loss
What the control is telling you
The flame went out during operation.
Applies to: Navien NPE-A2 (built-in recirculation) and NPE-S2 condensing tankless water heaters: NPE-150S2, NPE-180A2/S2, NPE-210A2/S2, NPE-240A2/S2
Likely causes
- Dirty air intake filter
- Poor electrical ground
- Low or dropping gas pressure under load
- Blocked intake/exhaust
Test and repair steps
- Clean the air intake filter (top left inside the cabinet, held by one screw); the manual suggests cleaning it every 3-4 months.
- Make sure the power cord is properly grounded.
- Measure inlet gas pressure at max fire 3.5-10.5 in. WC natural gas, 8.0-13 in. WC propane; look for a large drop when other appliances run.
- Inspect intake and exhaust terminations for blockage, snow or ice.
- Check Installer Menu > 1. Service Status Info > Flam Loss count to see how often it happens.
- Reset once with the Back button on the front panel and note whether the code returns.
- Code back after a reset? Stay at the unit and phone Navien Technical Support, 1-800-519-8794.
Settings for these units
- Installation clearances (indoor / outdoor) · Navien NPE-2
- Water quality limits and flushing schedule · Navien NPE-2
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NPE-A2/S2 User's Information Manual (20049624A), 5.2 Understanding Error Codes, p.17. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.