Goodman air handler error codes

20 codes with causes and test steps.

CodeMeaningSeverity
E0FCondensate switch open - high water in drain panMedium
E05Air handler fuse openHigh
Eb0Blower motor not running with a demand presentHigh
Eb1Control lost communication with the blower motorHigh
Eb2Motor horsepower does not match shared dataHigh
Eb3Blower limiting on power, temperature or speedMedium
Eb4Blower motor lost rotor control or high currentHigh
Eb5Blower motor failed to start 10 timesHigh
Eb6Blower shut down for voltage or power module temperatureHigh
Eb7Blower motor missing shared data / failed to start 40 timesHigh
Eb9Airflow lower than demandedMedium
EC1Communication error with the outdoor unitHigh
Ed0No shared data on the networkHigh
Ed1Invalid shared dataHigh
Ed4Shared data rejected by the controlHigh
RDS 2 flashesControl board internal fault (leak detection board)High
RDS 3 flashesR32 sensor communication faultHigh
RDS 4 flashesR32 sensor internal faultHigh
RDS fast flashR-32 leak alarm (or system verification test)Critical
RDS steady onDelay mode after leak alarm or faultMedium

Models covered

ACSF****13**AAAMST***U1300AAAVPTC183014AVPTC25B14AVPTC29B14AVPTC313714AVPTC31C14AVPTC31C14ADAVPTC33C14AVPTC35B14AVPTC37B14AVPTC37C14AVPTC37D14AVPTC39C14AVPTC426014AVPTC49C14AVPTC49D14AVPTC59C14AVPTC59D14AVPTC61D14AWSF****13**AAAWST****13**AAMBVC1201MBVC1601MBVC2001

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.