Goodman · Air handler
RDS fast flash R-32 leak alarm (or system verification test)
What the control is telling you
Red LED on the A2L board flashing fast. Either the sensor is detecting R-32 right now, or a technician started the 5-minute verification test. During an alarm the board stops the thermostat call, runs the blower and turns off electric heat.
Applies to: R-32 air handlers with refrigerant detection system (A2L PCB + R32 sensor): AMST, AWSF/AWST, ACSF
Likely causes
- Refrigerant leak at the indoor coil or nearby
- Verification test started (button pressed twice within 5 s)
Test and repair steps
- Warning: If a leak alarm is active, do not open or turn off the unit; ventilate and keep ignition sources away.
- If a verification test was started it ends by itself after 5 minutes, or press the button once to end it early.
- For a real alarm, the sensor and board are working - locate the leak and repair it.
- After repair, check system pressures and lines for leaks and confirm cooling and heating performance.
Models that show this code
4 models in Goodman/Amana R-32 AMST/AWSF/ACSF air handlers
Other codes on the same units
- RDS 4 flashes R32 sensor internal fault
- RDS slow flash Normal operation - leak detection OK
- RDS steady on Delay mode after leak alarm or fault
- RDS test mode System verification test (simulated leak)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman RS6200301 R-32 GLXS/ALXS/GLZS/ALZS service (07-2024), A2L PCB Fault Code and Recommended Action table p.25-26. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.