Goodman · Air handler
RDS test mode System verification test (simulated leak)
What the display is showing
Lets the contractor simulate an R-32 leak alarm to prove the system reacts. The red LED then flashes fast, as in a real leak alarm. The test runs 5 minutes and then returns to normal operation for up to 5 minutes. No other action is needed.
Applies to: AMST/AWSF/ACSF R-32 air handlers
What to do
- Press the manual test button on the control board 2 times within 5 seconds
- The LED flashes fast and the control acts as if a leak were detected
- The test ends by itself after 5 minutes, or press the button once to stop it early
Models that show this code
4 models in Goodman/Amana R-32 AMST/AWSF/ACSF air handlers
Other codes on the same units
- RDS 4 flashes R32 sensor internal fault
- RDS fast flash R-32 leak alarm (or system verification test)
- RDS slow flash Normal operation - leak detection OK
- RDS steady on Delay mode after leak alarm or fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: R-32 GLXS/GLZS and AMST/AWSF service RS6200301, RDS A2L PCB FAULT CODE table p.25 and Recommended Action table p.26. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.