Goodman · Air handler
RDS steady on Delay mode after leak alarm or fault
What the control is telling you
Red LED on steady: the alarm or fault has cleared but the board stays in mitigation (blower on) for 5 minutes before going back to normal.
Applies to: R-32 air handlers with refrigerant detection system (A2L PCB + R32 sensor): AMST, AWSF/AWST, ACSF
Likely causes
- Recent leak alarm or board/sensor fault
Test and repair steps
- Wait 5 minutes for the board to return to normal operation.
- Check system pressures and lines for leaks.
- Re-check heating and cooling performance after any repair.
Models that show this code
4 models in Goodman/Amana R-32 AMST/AWSF/ACSF air handlers
Other codes on the same units
- RDS 4 flashes R32 sensor internal fault
- RDS fast flash R-32 leak alarm (or system verification test)
- RDS slow flash Normal operation - leak detection OK
- RDS test mode System verification test (simulated leak)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman RS6200301 R-32 GLXS/ALXS/GLZS/ALZS service (07-2024), A2L PCB Fault Code and Recommended Action table p.25-26. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.