Goodman · Air handler
EC1 Communication error with the outdoor unit
What the control is telling you
The air handler lost communication with the outdoor unit; the outdoor unit does not run.
Applies to: ComfortBridge communicating air handlers AVPTC**14 (B* revision board) and MBVC1201/1601/2001 modular blowers
Likely causes
- Wrong or poor low-voltage/communication wiring between indoor and outdoor units
- Outdoor control lost power while running
Test and repair steps
- Warning: Turn off power to the air handler before working on wiring or the blower.
- Check the 1, 2, R, C wiring between the units: correct terminals, one wire per terminal, tight connections, no shorts or breaks.
- Find out why the outdoor control lost power (breaker, disconnect, fuse).
- Press the learn button (about 2 seconds) or use the Lrn menu to restart communications.
Models that show this code
21 models in Goodman/Amana ComfortBridge AVPTC/MBVC
Other codes on the same units
- Eb5 Blower motor failed to start 10 times
- Eb6 Blower shut down for voltage or power module temperature
- Eb7 Blower motor missing shared data / failed to start 40 times
- Eb9 Airflow lower than demanded
- Ed1 Invalid shared data
- Ed4 Shared data rejected by the control
- HP1 Compressor heat, low stage (comm)
- HP2 Compressor heat, high stage (comm)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, Air Handler Troubleshooting Matrix (B*) p.59-60. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.