Goodman · Air handler

Eb5 Blower motor failed to start 10 times

High severity Goodman/Amana ComfortBridge AVPTC/MBVC

What the control is telling you

The blower failed to start 10 times in a row.

Applies to: ComfortBridge communicating air handlers AVPTC**14 (B* revision board) and MBVC1201/1601/2001 modular blowers

Likely causes

  • Obstruction in the blower housing
  • Seized motor bearings
  • Failed blower motor

Test and repair steps

  1. Warning: Turn off power to the air handler before working on wiring or the blower.
  2. Check the wheel and housing for obstructions; repair or replace wheel/motor as needed.
  3. Spin the motor shaft by hand; replace the motor if it is tight or seized.

Models that show this code

21 models in Goodman/Amana ComfortBridge AVPTC/MBVC

AVPTC183014AVPTC25B14AVPTC29B14AVPTC313714AVPTC31C14AVPTC31C14ADAVPTC33C14AVPTC35B14AVPTC37B14AVPTC37C14AVPTC37D14AVPTC39C14AVPTC426014AVPTC49C14AVPTC49D14AVPTC59C14AVPTC59D14AVPTC61D14MBVC1201MBVC1601MBVC2001

Other codes on the same units

  • Eb0 Blower motor not running with a demand present
  • Eb1 Control lost communication with the blower motor
  • Eb2 Motor horsepower does not match shared data
  • Eb4 Blower motor lost rotor control or high current
  • Eb6 Blower shut down for voltage or power module temperature
  • Eb7 Blower motor missing shared data / failed to start 40 times
  • Eb9 Airflow lower than demanded
  • EC1 Communication error with the outdoor unit

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, Air Handler Troubleshooting Matrix (B*) p.59-60. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.