Goodman · Air handler
Eb0 Blower motor not running with a demand present
What the control is telling you
The circulator blower does not run even though there is a call.
Applies to: ComfortBridge communicating air handlers AVPTC**14 (B* revision board) and MBVC1201/1601/2001 modular blowers
Likely causes
- Loose or disconnected motor power leads
- Open or poorly connected inductor (3/4 HP and 1 HP models)
- Failed blower motor
Test and repair steps
- Warning: Turn off power to the air handler before working on wiring or the blower.
- Tighten or correct the motor power connections.
- On 3/4 and 1 HP models check the inductor for continuity and its connections; replace if open or shorted.
- Check the blower motor; replace if failed.
Models that show this code
21 models in Goodman/Amana ComfortBridge AVPTC/MBVC
Other codes on the same units
- AC2 Compressor cooling, high stage (comm)
- df1 Defrost, low-stage electric heat
- df2 Defrost, high-stage electric heat
- E05 Air handler fuse open
- Eb1 Control lost communication with the blower motor
- Eb2 Motor horsepower does not match shared data
- Eb4 Blower motor lost rotor control or high current
- Eb5 Blower motor failed to start 10 times
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, Air Handler Troubleshooting Matrix (B*) p.59-60. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.