Eb1 Control lost communication with the blower motor
What the control is telling you
The air handler control can no longer talk to the serial communicating blower motor.
Applies to: ComfortBridge communicating air handlers AVPTC**14 (B* revision board) and MBVC1201/1601/2001 modular blowers
Likely causes
- Loose motor control (4-wire) connection
- Failed blower motor
- Failed air handler control
Test and repair steps
- Warning: Turn off power to the air handler before working on wiring or the blower.
- Check and tighten the 4-wire motor control harness.
- Check voltages on the 4-wire harness (Specs tab: pins 1-4 and 1-2 about 3.3 VDC, 3-4 about 15 VDC).
- Replace the motor or the control, whichever is at fault.
Models that show this code
21 models in Goodman/Amana ComfortBridge AVPTC/MBVC
Other codes on the same units
- df1 Defrost, low-stage electric heat
- df2 Defrost, high-stage electric heat
- E05 Air handler fuse open
- Eb0 Blower motor not running with a demand present
- Eb2 Motor horsepower does not match shared data
- Eb4 Blower motor lost rotor control or high current
- Eb5 Blower motor failed to start 10 times
- Eb6 Blower shut down for voltage or power module temperature
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, Air Handler Troubleshooting Matrix (B*) p.59-60. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.