Bosch boiler error codes

49 codes (18 faults, 31 normal display and menu codes).

CodeMeaningSeverity / type
000-199Supply temperature readoutNormal status
2.CService function 2.C - purging functionMenu / mode display
2.FService function 2.F - temporary test operating modeMenu / mode display
4.EService function 4.E - appliance type detectedMenu / mode display
4.FService function 4.F - trap filling routineMenu / mode display
5.AService function 5.A - reset service-due indicationMenu / mode display
6.AService function 6.A - latest fault codeMenu / mode display
6.CService function 6.C - target supply temperature from outdoor resetMenu / mode display
6.bService function 6.b - room control voltage at terminal 2Menu / mode display
6.dService function 6.d - DHW turbine flow rateMenu / mode display
7.AService function 7.A - burner and fault indicator lampMenu / mode display
7.EService function 7.E - building drying functionMenu / mode display
7.bService function 7.b - 3-way valve to center positionMenu / mode display
8.AService function 8.A - software versionMenu / mode display
8.CService function 8.C - gas burner control (GFA) statusMenu / mode display
8.EService function 8.E - restore factory settingsMenu / mode display
8.FService function 8.F - permanent ignition testMenu / mode display
8.bService function 8.b - code plug numberMenu / mode display
8.dService function 8.d - gas burner control (GFA) faultMenu / mode display
9.AService function 9.A - constant operating modeMenu / mode display
9.CService function 9.C - current boiler outputMenu / mode display
9.bService function 9.b - current fan speedMenu / mode display
A7DHW temperature sensor faultMedium
A8Communication faultMedium
b1Code plug not detectedMedium
b2/b3/b4/b5/b6Internal data errorMedium
b7Burner control faultMedium
C6Fan not runningHigh
d3High limit / temperature limiter circuit openHigh
d5External supply temperature sensor fault (low-loss header)Medium
E2Supply temperature sensor faultHigh
E3Additional supply temperature sensor faultMedium
E9Safety high limit or flue gas limiter trippedHigh
F0Internal faultMedium
F1Internal data errorMedium
F7Flame detected with burner offHigh
A.CService function A.C - DHW tank temperatureMenu / mode display
A.bService function A.b - DHW temperatureMenu / mode display
AdDHW tank temperature not detectedMedium
C.dService function C.d - current heat demandMenu / mode display
DHW setpoint flashingSet DHW temperature flashing on displayNormal status
Display offDisplay dark - appliance switched offNormal status
EANo flame detectedHigh
ECO button litECO button lit - economy / alternating modeNormal status
Emissions test buttonEmissions test (chimney sweep) buttonMenu / mode display
FAFlame detected after gas shut offCritical
FdReset button pressed by mistakeLow
Key pad lock buttonKey pad lockMenu / mode display
Service buttonService button - open service functionsMenu / mode display

Models covered

ZBR21-3AZBR28-3AZBR35-3AZBR42-3A

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.