Bosch · Boiler

b7 Burner control fault

Medium severity Bosch Greenstar

What the control is telling you

A fault in the burner controls was detected.

Applies to: Bosch Greenstar ZBR 21/28/35/42-3A boilers and ZWB 28/35/42-3A combi boilers

Likely causes

  • Corrupted control data

Test and repair steps

  1. Warning: Disconnect mains power and close the gas cock before opening the appliance or working on the gas train.
  2. Restore factory defaults with service function 8.E, then reload the commissioning settings.
  3. Replace the PCB if it returns.

Models that show this code

4 models in Bosch Greenstar

ZBR21-3AZBR28-3AZBR35-3AZBR42-3A

Other codes on the same units

  • A7 DHW temperature sensor fault
  • A8 Communication fault
  • b1 Code plug not detected
  • b2/b3/b4/b5/b6 Internal data error
  • C6 Fan not running
  • d3 High limit / temperature limiter circuit open
  • d5 External supply temperature sensor fault (low-loss header)
  • E2 Supply temperature sensor fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Bosch Greenstar ZBR/ZWB 21-42-3A service manual 6721853955 (2025-11), Table 38 Faults shown on the display, p.74-75; Greenstar combi 100 p/151 p service manual 6721853953 (2025-11), Table 33. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.