Bosch · Boiler

b1 Code plug not detected

Medium severity Bosch Greenstar

What the control is telling you

The control cannot find the code plug.

Applies to: Bosch Greenstar ZBR 21/28/35/42-3A boilers and ZWB 28/35/42-3A combi boilers

Likely causes

  • Code plug not seated
  • Damaged code plug

Test and repair steps

  1. Warning: Disconnect mains power and close the gas cock before opening the appliance or working on the gas train.
  2. Push the code plug fully into its socket.
  3. Replace the code plug if the fault stays.

Models that show this code

4 models in Bosch Greenstar

ZBR21-3AZBR28-3AZBR35-3AZBR42-3A

Other codes on the same units

  • 9.C Service function 9.C - current boiler output
  • 9.b Service function 9.b - current fan speed
  • A7 DHW temperature sensor fault
  • A8 Communication fault
  • b2/b3/b4/b5/b6 Internal data error
  • b7 Burner control fault
  • C6 Fan not running
  • d3 High limit / temperature limiter circuit open

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Bosch Greenstar ZBR/ZWB 21-42-3A service manual 6721853955 (2025-11), Table 38 Faults shown on the display, p.74-75; Greenstar combi 100 p/151 p service manual 6721853953 (2025-11), Table 33. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.