Bosch · Boiler

EA No flame detected

High severity Bosch Greenstar

What the control is telling you

The burner did not light or flame was not proven within the safety time.

Applies to: Bosch Greenstar ZBR 21/28/35/42-3A boilers and ZWB 28/35/42-3A combi boilers

Likely causes

  • Gas cock closed or low gas pressure
  • Ground lead loose
  • Damaged electrodes
  • Blocked flue or condensate trap
  • Gas/air ratio out of range
  • Faulty gas valve
  • Soiled heat exchanger
  • Code plug problem

Test and repair steps

  1. Warning: Disconnect mains power and close the gas cock before opening the appliance or working on the gas train.
  2. Check the earth lead and the power supply.
  3. Confirm the gas cock is open and measure inlet gas pressure.
  4. Inspect the electrodes and replace if damaged.
  5. Check the flue system and clean the condensate trap.
  6. Remove and inspect the diaphragm at the fan inlet for dirt or cracks.
  7. Check the gas/air ratio and the gas valve; inspect the heat exchanger for soot.
  8. In room-air operation, check the combustion air openings; reseat the code plug.

Models that show this code

4 models in Bosch Greenstar

ZBR21-3AZBR28-3AZBR35-3AZBR42-3A

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Bosch Greenstar ZBR/ZWB 21-42-3A service manual 6721853955 (2025-11), Table 38 Faults shown on the display, p.74-75; Greenstar combi 100 p/151 p service manual 6721853953 (2025-11), Table 33. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.