Bosch · Boiler
Ad DHW tank temperature not detected
What the control is telling you
The tank sensor was recognised earlier but the connection to it has now been lost.
Applies to: Bosch Greenstar ZBR 21/28/35/42-3A boilers and ZWB 28/35/42-3A combi boilers
Likely causes
- Tank sensor disconnected or lead broken
Test and repair steps
- Warning: Disconnect mains power and close the gas cock before opening the appliance or working on the gas train.
- Check the tank sensor and its lead; replace if defective.
- If the sensor is fine, restore factory defaults with service function 8.E and re-enter the commissioning settings.
Models that show this code
4 models in Bosch Greenstar
Other codes on the same units
- F1 Internal data error
- F7 Flame detected with burner off
- A.C Service function A.C - DHW tank temperature
- A.b Service function A.b - DHW temperature
- C.d Service function C.d - current heat demand
- DHW setpoint flashing Set DHW temperature flashing on display
- Display off Display dark - appliance switched off
- EA No flame detected
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Bosch Greenstar ZBR/ZWB 21-42-3A service manual 6721853955 (2025-11), Table 38 Faults shown on the display, p.74-75; Greenstar combi 100 p/151 p service manual 6721853953 (2025-11), Table 33. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.