Bosch · Boiler

2.C Service function 2.C - purging function

Menu / mode display Bosch Greenstar

What the display is showing

Starts the air-purge routine by hand, for example after servicing. Values: 00 off, 01 purge once then returns to 00, 02 permanently on. During the purge the display alternates a symbol with the supply temperature.

Applies to: Greenstar ZBR/ZWB 21-42-3A wall-hung boilers and ZWB 28-42-3A combis

What to do

  1. Open service functions with the service button, scroll with the key pad lock / ECO buttons
  2. Select 2.C and press the emissions test button
  3. Choose 01 and save by holding the emissions test button

Models that show this code

4 models in Bosch Greenstar

ZBR21-3AZBR28-3AZBR35-3AZBR42-3A

Other codes on the same units

  • 000-199 Supply temperature readout
  • 2.F Service function 2.F - temporary test operating mode
  • 4.E Service function 4.E - appliance type detected
  • 4.F Service function 4.F - trap filling routine
  • 5.A Service function 5.A - reset service-due indication
  • 6.A Service function 6.A - latest fault code
  • 6.C Service function 6.C - target supply temperature from outdoor reset
  • 6.b Service function 6.b - room control voltage at terminal 2

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Bosch Greenstar wall ZBR-ZWB 21-42-3A service 6721853955 (2025-11) (same content in combi service 6721853953), 11.3 Description of the service functions pp.59-64. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.