Bosch · Boiler
E9 Safety high limit or flue gas limiter tripped
What the control is telling you
A heat exchanger safety limit or the flue gas temperature limiter has opened. The same code is used when the pump has seized.
Applies to: Bosch Greenstar ZBR 21/28/35/42-3A boilers and ZWB 28/35/42-3A combi boilers
Likely causes
- Faulty limiter or wiring
- Low system pressure or trapped air
- Pump capacitor weak or pump seized
- Blown PCB fuse
- Clogged DHW side of the heat exchanger
Test and repair steps
- Warning: Disconnect mains power and close the gas cock before opening the appliance or working on the gas train.
- Check both the flue gas limiter and heat exchanger limiter and their leads.
- Check the system operating pressure and purge the appliance.
- Check the pump capacitor and replace the pump if bad.
- Check the PCB fuse (6.3 A per IEC) and replace if blown.
- Check the DHW side of the heat exchanger and replace if blocked.
Models that show this code
4 models in Bosch Greenstar
Other codes on the same units
- d3 High limit / temperature limiter circuit open
- d5 External supply temperature sensor fault (low-loss header)
- E2 Supply temperature sensor fault
- E3 Additional supply temperature sensor fault
- F0 Internal fault
- F1 Internal data error
- F7 Flame detected with burner off
- A.C Service function A.C - DHW tank temperature
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Bosch Greenstar ZBR/ZWB 21-42-3A service manual 6721853955 (2025-11), Table 38 Faults shown on the display, p.74-75; Greenstar combi 100 p/151 p service manual 6721853953 (2025-11), Table 33. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.