Weil-McLain · Boiler · Startup

Pre-start and startup sequence

SlimFit Series 3

What happens, in order

  1. Read the control setup instructions and confirm the boiler model is set correctly in the control.
  2. Confirm the boiler and system are full of water and components are set for operation.
  3. Fill the condensate trap with water.
  4. Verify electrical connections are correct and secure.
  5. Inspect vent and air piping for corrosion, damage or sagging.
  6. Check for gas leaks with a detector or by smell, and do not start if a leak is found.
  7. Turn the boiler ON/OFF switch off.
  8. Follow the operating instructions in Figure 75.
  9. When first powered, confirm the control shows the expected sensors. If not, find the cause before continuing.

Codes you may see during this

Ignition Fault

Applies to: SlimFit SF-550 and SF-750 Series 3

Models

SF-550SF-750

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit series3 boiler manual, p. 85. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.