Weil-McLain · Boiler · Startup
Closure switch (flow switch or CAD) proof sequence
What happens, in order
- On a call for heat, the corresponding outputs energize.
- The blower does not start until the proof of closure switch closes and conducts.
- If the switch opens before ignition, the timer keeps running and the blower stays active.
- If the switch is still open after the timeout, the control locks out.
- If the switch opens during burner firing, the control locks out.
- The lockout clears when the closure switch returns to closed.
- The outputs stay energized while the control tries to close the switch.
Timings and thresholds
| Item | Value |
|---|---|
| Time allowed for closure switch to close | 4 minutes |
Applies to: Flow switch or combustion air damper interlock on P11 jumper
Models
SF1000SF1500SF2000
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist · Startup
- Final verification checklist and natural gas input check · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 56. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.