Viessmann · Boiler · Heating

Reduced heat-up boost on return to standard room temperature

Vitodens 200-W

What happens, in order

  1. When switching from reduced to standard room temperature, the supply temperature follows the selected heating curve.
  2. Coding address FA sets an extra increase of the set boiler water or supply temperature.
  3. Coding address FB sets how long the raised temperature is held.
  4. Example from manual FA gives 50 C + 20% = 60 C, and FB is 60 minutes.

Timings and thresholds

ItemValue
Example boost temperature (FA)60 C (50 C + 20%)
Example boost duration (FB)60 minutes

Codes you may see during this

FA FB

Applies to: Heating curve operation with reduced room temperature

Models

B2HB 45B2HB 57B2HB 160B2HB 199

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB service manual, p. 90. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.