Viessmann · Boiler · Startup

Commissioning assistant at first start-up

Vitotronic 300 GW6B

What happens, in order

  1. Turn ON the ON/OFF switch on all control units. The commissioning assistant starts automatically.
  2. Set Language, Date / Time and Temperature units.
  3. Tap Application and select single boiler, lead boiler and cascade, or lag boiler.
  4. Confirm with OK until the symbol and Setup appear.
  5. Tap Yes to set the important coding during commissioning, or No if no further settings are needed.
  6. Confirm with OK. A single boiler shows the standard menu; a multi boiler system shows the default display.
  7. If commissioning fails, a fault symbol appears in the footer. Tap it and check the fault messages.

Applies to: Vitotronic 300 GW6B, all applications

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW6B installation and service manual, p. 48. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.