Matching the control unit to a two-stage burner

Vitotronic 100 GC1

What happens, in order

  1. Start the burner.
  2. Set the override switch to the position shown in the manual.
  3. Note the maximum burner output from fuel consumption and record it.
  4. Set the override switch to position a.
  5. Press 9 and OK together for about 2 seconds to start the relay test.
  6. Activate burner stage 1 ON (display shows 4).
  7. Note the minimum burner output (basic load) from fuel consumption and record it.
  8. Press the button shown to end the relay test.
  9. Enter the recorded values in coding 1 (table on this page; see also page 154).

Applies to: Vitotronic 100 GC1 with two-stage burner

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 96. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.