Viessmann · Boiler · Startup

Initial start-up sequence after installation

Vitorond 200VD2A

What happens, in order

  1. Open the oil or gas supply valves.
  2. Switch on the system, heating pump and burner power supplies, following the burner maker's instructions.
  3. On a cold start, or after a long service stop, close the heating system supply so the boiler passes the dew point quickly.
  4. Once supply water is above the minimum temperature, slowly open the boiler supply and return valves to the heating system.
  5. Switch the burner to automatic.
  6. Check all gaskets and connections and retighten where needed.
  7. Several days after start-up, recheck and retighten the combustion chamber door and clean-out cover bolts.

Applies to: Vitorond 200 VD2A boilers

Models

VD2A-125VD2A-160VD2A-195VD2A-230VD2A-270

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2A installation manual, p. 35. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.