Viessmann · Boiler · Startup
Lighting and operating instructions
What happens, in order
- Set the thermostat or operating control to the lowest setting.
- Turn off all electric power to the appliance.
- Close the main gas shut-off valve.
- Wait five minutes to clear out any gas, then smell for gas including near the floor.
- If gas is smelled, stop and follow the gas smell steps.
- Open the main gas shut-off valve.
- Turn on all electric power to the appliance.
- Set the thermostat or operating control to the desired setting.
- If the appliance will not operate, shut off gas to the appliance and call the service technician or gas supplier.
Timings and thresholds
| Item | Value |
|---|---|
| Wait before reopening gas to clear gas | 5 minutes |
Applies to: Vitodens 200-W B2HB boilers with gas burner. Boiler has no pilot; ignition is automatic.
Models
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Matching the control unit to a modulating burner · Startup
- Matching the control unit to a two-stage burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB installation manual, p. 63. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.