Viessmann · Boiler · Startup

Control commissioning start-up

Versatronik 300

What happens, in order

  1. Mount the unit on a surface using field-supplied hardware.
  2. Connect the outdoor sensor if required, the common supply/LLH sensor, and the return sensor if used.
  3. Make low voltage external connections if required: demand function, 0-10VDC input, interlock disable.
  4. Make 120VAC output connections supply pump, AUX output (heat demand or combustion air), fault output.
  5. Program the outdoor reset menu (enable/disable, slope, shift, WWSD).
  6. Program boiler configuration number of boilers and LON addresses for each programmed boiler.
  7. Set specifications C/F units, AUX mode (demand or 0-10VDC), demand set point if needed, interlock, and return sensor.
  8. Confirm the set point shows on the display with an R (reset) or A (AUX) prefix.
  9. Confirm the boilers receive the set point and fire on temperature demand. The set point sent to the boilers can be checked in the main menu or in boiler diagnosis mode.
  10. Remember that boiler modulation is controlled by the boiler, not the Versatronik 300.

Applies to: Versatronik 300 cascade control

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 300 Cascade Control manual, p. 34. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.