Viessmann · Boiler · Startup

Boiler startup protection

Versatronik 200

What happens, in order

  1. Boiler below startup protection temperature: keep circulation pumps off.
  2. Keep the mixing valves shut.
  3. Once the boiler reaches the startup temperature, release the pumps and mixing valves.

Timings and thresholds

ItemValue
Startup protection temperature10°C - 85°C, standard 35°C

Applies to: Versatronik 200, heat source (not in cascade operation)

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 200 installation and operating manual, p. 138. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.