Viessmann · Boiler · Startup
Boiler startup protection
What happens, in order
- Boiler below startup protection temperature: keep circulation pumps off.
- Keep the mixing valves shut.
- Once the boiler reaches the startup temperature, release the pumps and mixing valves.
Timings and thresholds
| Item | Value |
|---|---|
| Startup protection temperature | 10°C - 85°C, standard 35°C |
Applies to: Versatronik 200, heat source (not in cascade operation)
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
- Matching the control unit to a two-stage burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 200 installation and operating manual, p. 138. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.