AUX output as combustion air function

Versatronik 300

What happens, in order

  1. On a call for heat, AUX turns on to drive a damper or blower rated for 120VAC.
  2. The control waits for a proving signal on the INT input. This must be a dry contact.
  3. Once proven, the boiler plant is allowed to continue operating.
  4. If no proving signal arrives in time, an alarm is triggered.

Timings and thresholds

ItemValue
AUX wait timer60 minutes (adjustable)

Applies to: Versatronik 300 AUX combustion air mode

More Viessmann boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 300 Cascade Control manual, p. 30. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.