Viessmann · Boiler · Startup
AUX output as combustion air function
What happens, in order
- On a call for heat, AUX turns on to drive a damper or blower rated for 120VAC.
- The control waits for a proving signal on the INT input. This must be a dry contact.
- Once proven, the boiler plant is allowed to continue operating.
- If no proving signal arrives in time, an alarm is triggered.
Timings and thresholds
| Item | Value |
|---|---|
| AUX wait timer | 60 minutes (adjustable) |
Applies to: Versatronik 300 AUX combustion air mode
More Viessmann boiler sequences
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a modulating burner · Startup
- Matching the control unit to a two-stage burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 300 Cascade Control manual, p. 30. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.