Viessmann · Boiler · Startup
Matching the control unit to a modulating burner
What happens, in order
- The burner must be fully adjusted first. Set the minimum output as low as possible, while observing the chimney and flue gas system.
- Start the burner.
- Set the override switch to the position shown in the manual.
- Wait until the burner actuator reaches maximum output.
- Note the maximum burner output from fuel consumption and record it.
- Press 9 and OK together for about 2 seconds to start the relay test.
- Activate the modulating burner close function (display shows 4) and set the override switch to a. Time how long the actuator takes to reach minimum output and record it.
- Note the minimum burner output (basic load) from fuel consumption and record it.
- Activate the modulating burner open function (display shows 2). After one third of the time measured in the previous step, set the modulating burner neutral function (display shows 3) to stop the actuator.
- Note the partial output from fuel consumption and record it.
- End the relay test with the button shown.
- Enter the recorded values in coding 1 (table on this page and page 154).
Timings and thresholds
| Item | Value |
|---|---|
| Actuator run time to minimum output | Measured in the close step; neutral is set after one third of this time |
Applies to: Vitotronic 100 GC1 with modulating burner
More Viessmann boiler sequences
- AUX output as combustion air function · Startup
- Boiler startup protection · Startup
- Commissioning assistant at first start-up · Startup
- Control commissioning start-up · Startup
- Initial start-up preparation · Startup
- Initial start-up sequence after installation · Startup
- Lighting and operating instructions · Startup
- Matching the control unit to a two-stage burner · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 97. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.