Viessmann · Boiler
Fb Combustion chamber pressure too high
What the control is telling you
Burner control is in a fault state.
Applies to: Vitocrossal 200 CM2 burner control unit
Likely causes
- Flue gas path or condensate path blocked
- Motorized vent damper not configured with the control (if used)
Test and repair steps
- Check and clean the flue gas path or condensate path.
- If a motorized vent damper is used, check its setting for a common vent system.
Models that show this code
13 models in Vitocrossal 200 CM2
Other codes on the same units
Sequence of operation
What the unit does around this code, step by step.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 53. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.