Viessmann · Boiler

F F4 No flame during safety time

High severity Vitocrossal 200 CM2

What the control is telling you

No flame forms during the safety time and the ionization monitor sees no flame signal. This code has several possible causes, listed here in the manual's order.

Applies to: Vitocrossal 200 CM2 burner control unit

Likely causes

  • Ionization electrode misadjusted, unplugged, or ground fault in electrode or cable
  • Ignition electrode not set correctly, earth leakage, faulty ignition unit, or faulty burner control unit
  • Cracked insulation body on ignition or ionization electrode
  • Poor start-up characteristics: servomotor, servomotor cable, solenoid valve, or burner control output relay faulty
  • Incorrect gas type selected
  • Gas valve does not open
  • Combustion characteristics not ideal

Test and repair steps

  1. Insert the ionization electrode plug and check the cables.
  2. Adjust the ionization electrode (see p. 19).
  3. Adjust the ignition electrodes (see p. 19).
  4. Replace the ignition unit or burner control unit if faulty.
  5. Replace the ignition or ionization electrode if the insulation is cracked.
  6. Replace the connecting cable, servomotor, solenoid valve or burner control unit as needed.
  7. Adjust gas type (see p. 9).
  8. Check the connecting cable to the gas valve, and check or replace the gas valve.
  9. Adjust the burner (see from p. 15). If needed, adjust the setting screws with the burner OFF.

Models that show this code

13 models in Vitocrossal 200 CM2

186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX

Other codes on the same units

  • F F0 KM BUS communication error, emergency operation
  • F F1 Flue gas excess temperature
  • F F2 Boiler water temperature too high
  • F F3 Faulty flame signal at start-up or after post-purge
  • F F5 Air pressure switch 1 fault
  • F F6 No gas pressure at gas pressure switch
  • F F7 Air pressure switch 1 idle-state check fault
  • F F8 Flame goes out during operation

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 51-52. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.