Viessmann · Boiler
F F0 KM BUS communication error, emergency operation
What the control is telling you
The control runs on internal default settings.
Applies to: Vitocrossal 200 CM2 burner control unit
Likely causes
- Communication error on the KM BUS to the burner control unit
Test and repair steps
- Check that the KM BUS cable plugs are firmly seated.
- Check all KM BUS cables.
Models that show this code
13 models in Vitocrossal 200 CM2
Other codes on the same units
- F EE Gas safety valve feedback error
- F EF Gas safety valve feedback error
- F F1 Flue gas excess temperature
- F F2 Boiler water temperature too high
- F F3 Faulty flame signal at start-up or after post-purge
- F F4 No flame during safety time
- F F5 Air pressure switch 1 fault
- F F6 No gas pressure at gas pressure switch
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 51. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.