Viessmann · Boiler

F F5 Air pressure switch 1 fault

High severity Vitocrossal 200 CM2

What the control is telling you

Air pressure switch 1 shows no air pressure with the fan off, or it switches off during operation.

Applies to: Vitocrossal 200 CM2 burner control unit

Likely causes

  • Air pressure switch 1 faulty, incorrectly connected or incorrectly set
  • Flue gas back pressure
  • Condensate build-up
  • Air pressure switch 1 hose faulty or leaking

Test and repair steps

  1. Replace or correctly connect and set air pressure switch 1.
  2. Remove flue gas back pressure.
  3. Check for condensate build-up.
  4. Reset the burner control unit.
  5. Replace the hose if faulty or leaking.

Models that show this code

13 models in Vitocrossal 200 CM2

186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX

Other codes on the same units

  • F F1 Flue gas excess temperature
  • F F2 Boiler water temperature too high
  • F F3 Faulty flame signal at start-up or after post-purge
  • F F4 No flame during safety time
  • F F6 No gas pressure at gas pressure switch
  • F F7 Air pressure switch 1 idle-state check fault
  • F F8 Flame goes out during operation
  • F F9 Fan speed or feedback fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 52. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.