Viessmann · Boiler
F F5 Air pressure switch 1 fault
What the control is telling you
Air pressure switch 1 shows no air pressure with the fan off, or it switches off during operation.
Applies to: Vitocrossal 200 CM2 burner control unit
Likely causes
- Air pressure switch 1 faulty, incorrectly connected or incorrectly set
- Flue gas back pressure
- Condensate build-up
- Air pressure switch 1 hose faulty or leaking
Test and repair steps
- Replace or correctly connect and set air pressure switch 1.
- Remove flue gas back pressure.
- Check for condensate build-up.
- Reset the burner control unit.
- Replace the hose if faulty or leaking.
Models that show this code
13 models in Vitocrossal 200 CM2
Other codes on the same units
- F F1 Flue gas excess temperature
- F F2 Boiler water temperature too high
- F F3 Faulty flame signal at start-up or after post-purge
- F F4 No flame during safety time
- F F6 No gas pressure at gas pressure switch
- F F7 Air pressure switch 1 idle-state check fault
- F F8 Flame goes out during operation
- F F9 Fan speed or feedback fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 52. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.