Viessmann · Boiler
F F1 Flue gas excess temperature
What the control is telling you
Burner control is in a fault state and the system cools down.
Applies to: Vitocrossal 200 CM2 burner control unit
Likely causes
- Flue gas temperature too high
- Excessive gas throughput
Test and repair steps
- Wait until the flue gas temperature drops below the permissible limit.
- Reset the burner control unit.
- Check the water level.
- Check the heat exchanger surfaces for contamination.
- Check the CO2 setting.
- Set gas throughput to the rated boiler heating output (see connection values, p. 18).
Models that show this code
13 models in Vitocrossal 200 CM2
Other codes on the same units
- F EE Gas safety valve feedback error
- F EF Gas safety valve feedback error
- F F0 KM BUS communication error, emergency operation
- F F2 Boiler water temperature too high
- F F3 Faulty flame signal at start-up or after post-purge
- F F4 No flame during safety time
- F F5 Air pressure switch 1 fault
- F F6 No gas pressure at gas pressure switch
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 51. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.