F F9 Fan speed or feedback fault
What the control is telling you
Fan not running, fan speed not reached, fan speed varies, or no fan feedback.
Applies to: Vitocrossal 200 CM2 burner control unit
Likely causes
- Fan faulty
- Cables faulty or broken, including cable a-OA
- Internal fault: fan cannot reach set value
- External power supply to fan not connected or faulty
- Fan blocked, possibly by a foreign object
Test and repair steps
- Check the cables, including cable a-OA.
- Check the external power supply to the fan.
- Replace the fan or the cable if required.
- Remove any foreign object blocking the fan.
- Replace the fan or burner control unit if the set value is never reached.
Models that show this code
13 models in Vitocrossal 200 CM2
Other codes on the same units
- F F2 Boiler water temperature too high
- F F3 Faulty flame signal at start-up or after post-purge
- F F4 No flame during safety time
- F F5 Air pressure switch 1 fault
- F F6 No gas pressure at gas pressure switch
- F F7 Air pressure switch 1 idle-state check fault
- F F8 Flame goes out during operation
- F b7 Coding card missing, incorrect or not matching
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 52-53. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.