Viessmann · Boiler
F b7 Coding card missing, incorrect or not matching
What the control is telling you
Burner control is in a fault state, the system cools down and the control locks out. Coding card problems are listed under this code.
Applies to: Vitocrossal 200 CM2 burner control unit
Likely causes
- Coding card not inserted in the burner control unit
- Incorrect or faulty coding card
- Coding card does not match the burner control unit
Test and repair steps
- Insert the coding card and check it.
- Replace the coding card if required.
- If the card does not match, replace the coding card or the burner control unit.
- Danger plug-in terminals are live. Only change the coding card with power isolated at the junction box.
Models that show this code
13 models in Vitocrossal 200 CM2
Other codes on the same units
- F F2 Boiler water temperature too high
- F F3 Faulty flame signal at start-up or after post-purge
- F F4 No flame during safety time
- F F5 Air pressure switch 1 fault
- F F6 No gas pressure at gas pressure switch
- F F7 Air pressure switch 1 idle-state check fault
- F F8 Flame goes out during operation
- F F9 Fan speed or feedback fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 50. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.