Weil-McLain · Boiler · Startup

Vent damper and burner ignition sequence (check)

EGPEG

What happens, in order

  1. Raise the room thermostat to call for heat; the vent damper actuator slowly opens the damper and the display shows OPENING DAMPER.
  2. When the vent damper is fully open, the pilot lights and then the main burners ignite; the display advances to PILOT IGNITION.
  3. Confirm the vent damper is fully open before the main burners light.
  4. Lower the thermostat; the main burner flames go out and the vent damper closes.
  5. The display shows POST PURGE until the damper end switch confirms it is closed.
  6. If the damper stays open, the display advances to STANDBY after about 15 seconds to allow operation with the damper hold open switch.
  7. Repeat these steps several times to verify operation.
  8. Return the thermostat to its normal setting.
  9. Set the thermostat heat anticipator to the value on the wiring diagram.

Timings and thresholds

ItemValue
Post purge display advances to STANDBY if damper stays openabout 15 seconds

Codes you may see during this

OPENING DAMPER PILOT IGNITION POST PURGE STANDBY

Applies to: EG / PEG water and steam boilers

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: EG / PEG Series 7 boiler manual, p. 60. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.