Uncrate and place the boiler
What happens, in order
- Move the crate to a solid, level surface with room for the ramp and final placement.
- Place the ramp end into the pallet notch and secure it to the pallet.
- Remove the board marked REMOVE TO UNLOAD.
- Remove the eight screws and eight lag bolts from the four shipping brackets.
- Roll the boiler down the ramp onto a solid, level surface. Apply pressure only at the jacket corner posts or water manifolds.
- Keep the boiler straight while rolling. The front casters swivel and the back casters are fixed.
- Lower the leveling legs until they contact the floor, then remove jacket panels as needed to reach the bolts.
- Adjust legs until the base is 1/16 in (1.6 mm) above the floor and the boiler is level front-to-back and side-to-side on the cover plate.
Applies to: SVF 500/600 boilers
Models
SVF 500SVF 600
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch (flow switch or CAD) proof sequence · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 boiler manual, p. 14-15. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.