Weil-McLain · Boiler · Startup

U-Control power-up check

Ultra Series 4

What happens, in order

  1. Check the boiler model on the power-up screen. If it is wrong, turn off the boiler and change it per Figure 115, page 102.
  2. Review the sensors the screen lists. If a sensor is missing, check its connection.
  3. If a sensor is not detected, turn power off, fix the connection, and restart.

Applies to: All Ultra models with U-Control

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Ultra Series 4 boiler manual, p. 32. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.