Weil-McLain · Boiler · Other

Type 1 additional heat demand delay sequence

Ultra Series 4

What happens, in order

  1. Boiler receives a call for heat and starts its startup sequence.
  2. The additional heat demand delay timer starts.
  3. When the delay timing ends, the U-Control closes P16 #6 and #7 to start the next heat source.

Timings and thresholds

ItemValue
Additional heat demand delay0 to 240 minutes (ADD'L HEAT DEMAND TIME)

Applies to: Ultra as primary heat source

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Ultra Series 4 boiler manual, p. 99 and p. 104. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.