Weil-McLain · Boiler · Other

Supply 60F > Return lockout retry timing

ECO Tec Series 3

What happens, in order

  1. First lockout clears after 2 min 30 s.
  2. Each later lockout adds 1 minute, up to the fifth lockout.
  3. After the fifth lockout the system retries every 6 min 30 s while temperatures stay below 60 F.
  4. If the burner runs at least 2 minutes without the difference exceeding 60 F, the timer resets to 2 min 30 s.

Timings and thresholds

ItemValue
First lockout2 min 30 s
Second lockout3 min 30 s
Third lockout4 min 30 s
Fourth lockout5 min 30 s
Fifth lockout6 min 30 s
Retry interval after fifth6 min 30 s

Codes you may see during this

Supply 60F > Return

Applies to: ECO Tec Series 3

Models

80110150199

More Weil-McLain boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 168. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.