Supply 60F > Return lockout retry timing
What happens, in order
- First lockout clears after 2 min 30 s.
- Each later lockout adds 1 minute, up to the fifth lockout.
- After the fifth lockout the system retries every 6 min 30 s while temperatures stay below 60 F.
- If the burner runs at least 2 minutes without the difference exceeding 60 F, the timer resets to 2 min 30 s.
Timings and thresholds
| Item | Value |
|---|---|
| First lockout | 2 min 30 s |
| Second lockout | 3 min 30 s |
| Third lockout | 4 min 30 s |
| Fourth lockout | 5 min 30 s |
| Fifth lockout | 6 min 30 s |
| Retry interval after fifth | 6 min 30 s |
Codes you may see during this
Supply 60F > Return
Applies to: ECO Tec Series 3
Models
80110150199
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist at commissioning · Startup
- Lighting and operating sequence · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 boiler manual, p. 168. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.