Weil-McLain · Boiler · Startup
Start-up check before firing the boiler
What happens, in order
- Check system piping for leaks; shut down and repair any found before continuing.
- Vent air from the system using the manual vents.
- Inspect the vent system for corrosion, physical damage or sagging; confirm masonry chimney liners are sound, unobstructed, and have no openings.
- Check around the boiler for gas odor using the leak-check procedure.
- Verify operation per the Operation Verification section and complete the Final Verification Checklist and installation certificate.
- If the boiler will not start, check loose connections, blown fuse or service switch, boiler temperature setting below water temperature, thermostat setting below room temperature, gas supply turned on at meter and boiler, and incoming gas pressure (not below 5 in. w.c. natural gas or 11 in. w.c. propane).
- If none of these fixes the problem, go to the troubleshooting section.
Applies to: CGi Series 5 gas-fired water boilers
Models
CGi-25 to CGi-8
More Weil-McLain boiler sequences
- Annual start-up checklist (service technician) · Startup
- Blower calibration at first startup · Startup
- Check flame and combustion with instruments · Startup
- Check flame and combustion with instruments at high fire, low fire and auto · Startup
- Closure switch (flow switch or CAD) proof sequence · Startup
- Closure switch interlock startup sequence · Startup
- Express Setup Example B wizard order (Combi with two zones) · Startup
- Final verification checklist · Startup
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: CGi Series 5 boiler manual, p. 64. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.